Special Thanks to http://electrical-engineering-portal.com/
Cable Capacity:
For Cu Wire Current Capacity (Up to 30 Sq.mm) = 6X Size of Wire in Sq.mm
Ex. For 2.5 Sq.mm=6×2.5=15 Amp, For 1 Sq.mm=6×1=6 Amp, For 1.5 Sq.mm=6×1.5=9 Amp
For Cable Current Capacity = 4X Size of Cable in Sq.mm ,Ex. For 2.5 Sq.mm=4×2.5=9 Amp.
Nomenclature for cable Rating = Uo/U
where Uo=Phase-Ground Voltage, U=Phase-Phase Voltage, Um=Highest Permissible Voltage
Current Capacity of Equipments:
1 Phase Motor draws Current=7Amp per HP.
3 Phase Motor draws Current=1.25Amp per HP.
Full Load Current of 3 Phase Motor=HPx1.5
Full Load Current of 1 Phase Motor=HPx6
No Load Current of 3 Phase Motor =30% of FLC
KW Rating of Motor=HPx0.75
Full Load Current of equipment =1.39xKVA (for 3 Phase 415Volt)
Full Load Current of equipment =1.74xKw (for 3 Phase 415Volt)
Earthing Resistance:
Earthing Resistance for Single Pit=5Ω ,Earthing Grid=0.5Ω
As per NEC 1985 Earthing Resistance should be <5Ω.
Voltage between Neutral and Earth <=2 Volts
Resistance between Neutral and Earth <=1Ω
Creepage Distance=18 to 22mm/KV (Moderate Polluted Air) or
Creepage Distance=25 to 33mm/KV (Highly Polluted Air)
Minimum Bending Radius:
Minimum Bending Radius for LT Power Cable=12xDia of Cable.
Minimum Bending Radius for HT Power Cable=20xDia of Cable.
Minimum Bending Radius for Control Cable=10xDia of Cable.
Insulation Resistance:
Insulation Resistance Value for Rotating Machine= (KV+1) MΩ.
Insulation Resistance Value for Motor (IS 732) = ((20xVoltage (L-L)) / (1000+ (2xKW)).
Insulation Resistance Value for Equipment (<1KV) = Minimum 1 MΩ.
Insulation Resistance Value for Equipment (>1KV) = KV 1 MΩ per 1KV.
Insulation Resistance Value for Panel = 2 x KV rating of the panel.
Min Insulation Resistance Value (Domestic) = 50 MΩ / No of Points. (All Electrical Points with Electrical fitting & Plugs). Should be less than 0.5 MΩ
Min Insulation Resistance Value (Commercial) = 100 MΩ / No of Points. (All Electrical Points without fitting & Plugs).Should be less than 0.5 MΩ.
Test Voltage (A.C) for Meggering = (2X Name Plate Voltage) +1000
Test Voltage (D.C) for Meggering = (2X Name Plate Voltage).
Submersible Pump Take 0.4 KWH of extra Energy at 1 meter drop of Water.
Lighting Arrestor:
Arrestor have Two Rating=
(1) MCOV=Max. Continuous Line to Ground Operating Voltage.
(2) Duty Cycle Voltage. (Duty Cycle Voltage>MCOV).
Transformer:
Current Rating of Transformer=KVAx1.4
Short Circuit Current of T.C /Generator= Current Rating / % Impedance
No Load Current of Transformer=<2% of Transformer Rated current
Capacitor Current (Ic)=KVAR / 1.732xVolt (Phase-Phase)
Typically the local utility provides transformers rated up to 500kVA For maximum connected load of 99kW,
Typically the local utility provides transformers rated up to 1250kVA For maximum connected load of 150kW.
The diversity they would apply to apartments is around 60%
Maximum HT (11kV) connected load will be around 4.5MVA per circuit.
4No. earth pits per transformer (2No. for body and 2No. for neutral earthing),
Clearances, approx.1000mm around TC allow for transformer movement for replacement.
Diesel Generator:
Diesel Generator Set Produces=3.87 Units (KWH) in 1 Litter of Diesel.
Requirement Area of Diesel Generator = for 25KW to 48KW=56 Sq.meter, 100KW=65 Sq.meter.
DG less than or equal to 1000kVA must be in a canopy.
DG greater 1000kVA can either be in a canopy or skid mounted in an acoustically treated room DG noise levels to be less than 75dBA @ 1meter.
DG fuel storage tanks should be a maximum of 990 Litter per unit Storage tanks above this level will trigger more stringent explosion protection provision.
Current Transformer:
Nomenclature of CT:
Ratio: input / output current ratio
Burden (VA): total burden including pilot wires. (2.5, 5, 10, 15 and 30VA.)
Class: Accuracy required for operation (Metering: 0.2, 0.5, 1 or 3, Protection: 5, 10, 15, 20, 30).
Accuracy Limit Factor:
Nomenclature of CT: Ratio, VA Burden, Accuracy Class, Accuracy Limit Factor.Example: 1600/5, 15VA 5P10 (Ratio: 1600/5, Burden: 15VA, Accuracy Class: 5P, ALF: 10)
As per IEEE Metering CT: 0.3B0.1 rated Metering CT is accurate to 0.3 percent if the connected secondary burden if impedance does not exceed 0.1 ohms.
As per IEEE Relaying (Protection) CT: 2.5C100 Relaying CT is accurate within 2.5 percent if the secondary burden is less than 1.0 ohm (100 volts/100A).
Quick Electrical Calculation
1HP=0.746KW
Star Connection
1KW=1.36HP
Line Voltage=√3 Phase Voltage
1Watt=0.846 Kla/Hr
Line Current=Phase Current
1Watt=3.41 BTU/Hr
Delta Connection
1KWH=3.6 MJ
Line Voltage=Phase Voltage
1Cal=4.186 J
Line Current=√3 Phase Current
1Tone= 3530 BTU
85 Sq.ft Floor Area=1200 BTU
1Kcal=4186 Joule
1KWH=860 Kcal
1Cal=4.183 Joule
Useful Equations:
For Sinusoidal Current : Form Factor = RMS Value/Average Value=1.11
For Sinusoidal Current : Peak Factor = Max Value/RMS Value =1.414
Average Value of Sinusoidal Current(Iav)=0.637xIm (Im= Max.Value)
RMS Value of Sinusoidal Current(Irms)=0.707xIm (Im= Max.Value)
A.C Current=D.C Current/0.636.
Phase Difference between Phase= 360/ No of Phase (1 Phase=230/1=360°,2Phase=360/2=180°)
Short Circuit Level of Cable in KA (Isc)=(0.094xCable Dia in Sq.mm)/√ Short Circuit Time (Sec)
Max.Cross Section Area of Earthing Strip(mm2) =√(Fault Current x Fault Current x Operating Time of Disconnected Device ) / K
K=Material Factor, K for Cu=159, K for Alu=105, K for steel=58 , K for GI=80
Most Economical Voltage at given Distance=5.5x√ ((km/1.6)+(kw/100))
Cable Voltage Drop(%)=(1.732xcurrentx(RcosǾ+jsinǾ)x1.732xLength (km)x100)/(Volt(L-L)x Cable Run.
Spacing of Conductor in Transmission Line (mm) = 500 + 18x (P-P Volt) + (2x (Span in Length)/50).
Protection radius of Lighting Arrestor = √hx (2D-h) + (2D+L). Where h= height of L.A, D-distance of equipment (20, 40, 60 Meter), L=Vxt (V=1m/ms, t=Discharge Time).
Size of Lighting Arrestor= 1.5x Phase to Earth Voltage or 1.5x (System Voltage/1.732).
Maximum Voltage of the System= 1.1xRated Voltage (Ex. 66KV=1.1×66=72.6KV)
Load Factor=Average Power/Peak Power
If Load Factor is 1 or 100% = This is best situation for System and Consumer both.
If Load Factor is Low (0 or 25%) =you are paying maximum amount of KWH consumption. Load Factor may be increased by switching or use of your Electrical Application.
Demand Factor= Maximum Demand / Total Connected Load (Demand Factor <1)
Demand factor should be applied for Group Load
Diversity Factor= Sum of Maximum Power Demand / Maximum Demand (Demand Factor >1)
Diversity factor should be consider for individual Load
Plant Factor(Plant Capacity)= Average Load / Capacity of Plant
Fusing Factor=Minimum Fusing Current / Current Rating (Fusing Factor>1).
Voltage Variation(1 to 1.5%)= ((Average Voltage-Min Voltage)x100)/Average Voltage
Ex: 462V, 463V, 455V, Voltage Variation= ((460-455) x100)/455=1.1%.
Current Variation(10%)= ((Average Current-Min Current)x100)/Average Current
Ex:30A,35A,30A, Current Variation=((35-31.7)x100)/31.7=10.4%
Fault Level at TC Secondary=TC (VA) x100 / Transformer Secondary (V) x Impedance (%)
Motor Full Load Current= Kw /1.732xKVxP.FxEfficiency
Size of Capacitor for P.F Correction:
For Motor
Size of Capacitor = 1/3 Hp of Motor ( 0.12x KW of Motor)
For Transformer
< 315 KVA
5% of KVA Rating
315 KVA to 1000 KVA
6% of KVA Rating
>1000 KVA
8% of KVA Rating
Earthing Resistance value:
Power Station
0.5 Ω
Sub Station Major
1.0 Ω
Sub Station Minor
2.0 Ω
Distribution Transformer
5.0 Ω
Transmission Line
10 Ω
Single Isolate Earth Pit
5.0 Ω
Earthing Grid
0.5 Ω
As per NEC Earthing Resistance should be <5.0 Ω
Voltage Limit (As per CPWD & Kerala Elect.Board):
Voltage Limit (As Per CPWD)
240V
< 5 KW
415V
<100 KVA
11KV
<3 MVA
22KV
<6 MVA
33KV
<12 MVA
66KV
<20 MVA
110KV
<40 MVA
220KV
>40 MVA
Voltage Variation
> 33 KV
(-) 12.5% to (+) 10%
< 33 KV
(-) 9% to (+) 6%
Low Voltage
(-) 6% to (+) 6%
Insulation Class:
Insulation
Temperature
Class A
105°C
Class E
120°C
Class B
130°C
Class F
155°C
Class H
180°C
Class N
200°C
Standard Voltage Limit:
Voltage
IEC (60038)
IEC (6100:3.6)
Indian Elect. Rule
ELV
< 50 V
LV
50 V to 1 KV
<=1 KV
< 250 V
MV
<= 35 KV
250 V to 650 V
HV
> 1KV
<= 230 KV
650 V to 33 KV
EHV
> 230 KV
> 33 KV
Standard Electrical Connection (As per GERC):
As per Type of Connection
Connection
Voltage
LT Connection
<=440V
HT connection
440V to 66KV
EHT connection
>= 66KV
As per Electrical Load Demand
Up 6W Load demand
1 Phase 230V Supply
6W to 100KVA(100KW)
3 Phase 440V Supply
100KVA to 2500KVA
11KV,22KV,33KV
Above 2500KVA
66KV
HT Connection Earthing
H.T Connection’s Earthing Strip
20mmX4mm Cu. Strip
CT & PT bodies
2Nos
PT Secondary
1Nos
CT Secondary
1Nos
I/C and O/G Cable+ Cubicle Body
2Nos
Standard Meter Room Size (As per GERC):
Meter Box Height
Upper level does not beyond 1.7 meter and Lower level should not
below 1.2 meter from ground.
Facing of Meter Box
Meter Box should be at front area of Building at Ground Floor.
Meter Room / Closed Shade
4 meter square Size
Approximate Load as per Sq.ft Area (As per DHBVN):
Sq.ft Area
Required Load (Connected)
< 900 Sq.ft
8 KW
901 Sq.ft to 1600 Sq.ft
16 KW
1601 Sq.ft to 2500 Sq.ft
20 KW
> 2500 Sq.ft
24 KW
For Flats :100 Sq.ft / 1 KW
For Flats USS /TC: 100 Sq.ft / 23 KVA
Contracted Load in case of High-rise Building:
For Domestic Load
500 watt per 100 Sq. foot of the constructed area.
For Commercial
1500 watt per 100 Sq. foot of the constructed area
For lift, water lifting pump, streetlight if any, corridor/campus
Other Common Load
lighting and other common facilities, actual load shall be
calculated
Staircase Light
11KW/Flat Ex: 200Flat=200×11=2.2KW
Sanctioned Load for Building
Up to 50 Kw
The L.T. existing mains shall be strengthened.
50 kW to 450 kW (500 kVA)
11 kV existing feeders shall be extended if spare capacity is
available otherwise, new 11 kV feeders shall be constructed.
450 kW to 2550 kW (3000 kVA)
11 kV feeder shall be constructed from the nearest 33 kV or 110
kV substation
2550 kW to 8500 kW (10,000 kVA)
33kV feeder from 33 kV or 110 kV sub station
8500 kW (10,000 kVA)
110 kV feeder from nearest 110 kV or 220 kV sub-station
Electrical Thumb Rules-(Part-4)
AUGUST 18, 2013 5 COMMENTS
Sub Station Capacity & Short Circuit Current Capacity:
As per GERC
Voltage
Sub Station Capacity
Short Circuit Current
400 KV
Up to 1000 MVA
40 KA (1 to 3 Sec)
220 KV
Up to 320 MVA
40 KA (1 to 3 Sec)
132 KV
Up to 150 MVA
32 KA (1 to 3 Sec)
66 KV
Up to 80 MVA
25 KA (1 to 3 Sec)
33 KV
1.5 MVA to 5 MVA
35 KA (Urban) (1 to 3 Sec)
11 KV
150 KVA to 1.5 MVA
25 KA (Rural) (1 to 3 Sec)
415 V
6 KVA to 150 KVA
10 KA (1 to 3 Sec)
220 V
Up to 6 KVA
6 KA (1 to 3 Sec)
Sub Station Capacity & Short Circuit Current Capacity:
As per Central Electricity Authority
Voltage
Sub Station Capacity
Short Circuit Current
765 KV
4500 MVA
31.5 KA for 1 Sec
400 KV
1500 MVA
31.5 KA for 1 Sec
220 KV
500 MVA
40 KA for 1 Sec
110/132 KV
150 MVA
40 KA or 50 KA for 1 Sec
66 KV
75 MVA
40 KA or 50 KA for 1 Sec
Minimum Ground Clearance and Fault Clearing Time:
Voltage
Min. Ground Clearance
Fault Clear Time
400 KV
8.8 Meter
100 mille second
220 KV
8.0 Meter
120 mille second
132 KV
6.1 Meter
160 mille second
66 KV
5.1 Meter
300 mille second
33 KV
3.7 Meter
11 KV
2.7 Meter
Bus bar Ampere Rating:
For Phase Bus bar
Aluminium 130 Amp / Sq.cm or 800Amp / Sq.inch.
For Phase Bus bar
Copper 160 Amp / Sq.cm or 1000Amp / Sq.inch
For Neutral Bus bar
Same as Phase Bus bar up to 200 Amp than Size of Neutral Bus bar is at
least half of Phase Bus bar.
Bus bar Spacing:
Between Phase and Earth
26mm (Min)
Between Phase and Phase
32mm (Min)
Bus bar Support between Two Insulator
250mm.
Sound Level of Diesel Generator (ANSI 89.2&NEMA 51.20):
KVA
Max. Sound Level
<9 KVA
40 DB
10 KVA to 50 KVA
45 DB
51 KVA to 150 KVA
50 DB
151 KVA to 300 KVA
55 DB
301 KVA to 500 KVA
60 DB
IR Value of Transformer:
IR Value of Transformer
Voltage
30°C
40°C
50°C
>66KV
600MΩ
300MΩ
150MΩ
22KV to 33KV
500MΩ
250MΩ
125MΩ
6.6KV to 11KV
400MΩ
200MΩ
100MΩ
<6.6KV
200MΩ
100MΩ
50MΩ
415V
100MΩ
50MΩ
20MΩ
Standard Size of MCB/MCCB/ELCB/RCCB/SFU/Fuse:
MCB Up to 63 Amp (80Amp and 100 Amp a per Request)
MCCB
Up to 1600 Amp (2000 Amp as per Request)
ACB
Above 1000 Amp
MCB Rating
6A,10A,16A,20A,32A,40A,50A,63A
MCCB Rating
0.5A,1A,2A,4A,6A,10A,16A,20A,32A,40A,50A,63A,80A,100A
(Domestic Max 6A)
RCCB/ELCB
6A,10A,16A,20A,32A,40A,50A,63A,80A,100A
Sen. of ELCB
30ma (Domestic),100ma (Industrial),300ma
DPIC (Double Pole Iron Clad)
5A,15A,30 A for 250V
main switch
TPIC (Triple Pole Iron Clad)
30A, 60A, 100A, 200 A For 500 V
main switch
DPMCB
5A, 10A, 16A, 32A and 63 A for 250V
TPMCCB
100A,200A, 300Aand 500 A For 660 V
TPN main switch
30A, 60A, 100A, 200A, 300 A For 500 V
TPNMCB
16A, 32A,63A For 500 V, beyond this TPNMCCB: 100A, 200A,
300A, 500 A For 660 V
TPN Fuse Unit (Rewirable)
16A,32A,63A,100A,200A
Change over switch (Off
32A,63A,100A,200A,300A,400A,630A,800A
Load)
SFU (Switch Fuse Unit)
32A,63A,100A,125A,160A,200A,250A,315A,400A,630A
HRC Fuse TPN (Bakelite)
125A,160A,200A,250A,400A.630A
HRC Fuse DPN (Bakelite)
16A,32A,63A
MCB/MCCB/ELCB Termination Wire / Cable
Up to 20A MCB
Max. 25 Sq.mm
20A to 63A MCB
Max. 35 Sq.mm
MCCB
Max. 25 Sq.mm
6A to 45A ELCB
16 Sq.mm
24A to 63A ELCB
35 Sq.mm
80A to 100A ELCB
50 Sq.mm
Electrical Thumb Rules-(Part-5)
SEPTEMBER 1, 2013 4 COMMENTS
Standard Size of Transformer (IEEE/ANSI 57.120):
Single Phase Transformer
Three Phase Transformer
5KVA,10 KVA,15 KVA,25 KVA,37.5
3 KVA,5 KVA,9 KVA,15 KVA,30 KVA,45 KVA,75
KVA,50 KVA,75 KVA,100 KVA,167
KVA,112.5 KVA,150 KVA,225 KVA,300 KVA,500 KVA,750
KVA,250 KVA,
KVA,1MVA,1.5 MVA,2 MVA,2.5 MVA,3.7 MVA,5
333 KVA,500 KVA,833 KVA,1.25
MVA,7.5MVA, 10MVA ,12MVA,15MVA,20MVA ,25MVA,
KVA,1.66 KVA,2.5 KVA,3.33 KVA,5.0
30MVA,37.5MVA ,50MVA ,60MVA,75MVA,100MVA
KVA,6.6 KVA,8.3 KVA,10.0 KVA,12.5
KVA,16.6 KVA,20.8 KVA,25.0
KVA,33.33 KVA
Standard Size of Motor (HP):
Electrical Motor (HP)
1,1.5,2,3,5,7.5,10,15,20,30,40,50,60,75,100,125,150,200,250,300,400,450,500,600,700,
800,900,1000,1250,1250,1500,1750,2000,2250,3000,3500,4000
Approximate RPM of Motor
HP
RPM
< 10 HP
750 RPM
10 HP to 30 HP
600 RPM
30 HP to 125 HP
500 RPM
125 HP to 300 HP
375 RPM
Standard Size of Motor (HP):
Electrical Motor (HP)
1,1.5,2,3,5,7.5,10,15,20,30,40,50,60,75,100,125,150,200,250,300,400,450,500,600,700,
800,900,1000,1250,1250,1500,1750,2000,2250,3000,3500,4000
Motor Line Voltage:
Motor (KW)
Line Voltage
< 250 KW
440 V (LV)
150 KW to 3000KW
2.5 KV to 4.1 KV (HV)
200 KW to 3000KW
3.3 KV to 7.2 KV (HV)
1000 KW to 1500KW
6.6 KV to 13.8 KV (HV)
Motor Starting Current:
Supply
Size of Motor
Max. Starting Current
1 Phase
< 1 HP
6 X Motor Full Load Current
1 Phase
1 HP to 10 HP
3 X Motor Full Load Current
3 Phase
10
HP
2 X Motor Full Load Current
3 Phase
10
HP to 15 HP
2 X Motor Full Load Current
3 Phase
> 15 HP
1.5 X Motor Full Load Current
Motor Starter:
Starter
HP or KW
Starting Current
Torque
DOL
<13 HP(11KW)
7 X Full Load Current
Good
Star-
13 HP to 48 HP
3 X Full Load Current
Poor
Delta
Auto TC
> 48 HP (37 KW)
4 X Full Load Current
Good/ Average
VSD
0.5 to 1.5 X Full Load Current
Excellent
Motor > 2.2KW Should not connect direct to supply voltage if it is in Delta winding
Impedance of Transformer (As per IS 2026):
MVA
% Impedance
< 1 MVA
5%
1 MVA to 2.5 MVA
6%
2.5 MVA to 5 MVA
7%
5 MVA to 7 MVA
8%
7 MVA to 12 MVA
9%
12 MVA to 30 MVA
10%
> 30 MVA
12.5%
Standard Size of Transformer:
Standard Size of Transformer
KVA
Power Transformer (Urban)
3,6,8,10,16
Power Transformer (Rural)
1,1.6,3.15,5
Distribution Transformer
25,50,63,100,250,315,400,500,630
Electrical Thumb Rules-(Part-6)
SEPTEMBER 5, 2013 9 COMMENTS
Transformer Earthing Wire / Strip Size:
Size of T.C or DG
Body Earthing
Neutral Earthing
<315 KVA
25×3 mm Cu / 40×6 mm GI Strip
25×3 mm Cu Strip
315 KVA to 500 KVA
25×3 mm Cu / 40×6 mm GI Strip
25×3 mm Cu Strip
500 KVA to 750 KVA
25×3 mm Cu / 40×6 mm GI Strip
40×3 mm Cu Strip
750 KVA to 1000 KVA
25×3 mm Cu / 40×6 mm GI Strip
50×3 mm Cu Strip
Motor Earthing Wire / Strip Size:
Size of Motor
Body Earthing
< 5.5 KW
85 SWG GI Wire
5.5 KW to 22 KW
25×6 mm GI Strip
22 KW to 55 KW
40×6 mm GI Strip
>55 KW
50×6 mm GI Strip
Panel Earthing Wire / Strip Size:
Type of Panel
Body Earthing
Lighting & Local Panel
25×6 mm GI Strip
Control & Relay Panel
25×6 mm GI Strip
D.G & Exciter Panel
50×6 mm GI Strip
D.G & T/C Neutral
50×6 mm Cu Strip
Electrical Equipment Earthing:
Equipment
Body Earthing
LA (5KA,9KA)
25×3 mm Cu Strip
HT Switchgear
50×6 mm GI Strip
Structure
50×6 mm GI Strip
Cable Tray
50×6 mm GI Strip
Fence / Rail Gate
50×6 mm GI Strip
Earthing Wire (As per BS 7671)
Cross Section Area of Phase, Neutral
Minimum Cross Section area of Earthing Conductor
Conductor(S) mm2
(mm2)
S<=16
S (Not less than 2.5 mm2)
16<S<=35
16
S>35
S/2
Area for Transformer Room: (As per NBC-2005):
Transformer
Min. Transformer
Min. Total Sub Station Area(
Min. Space
Size
Room Area (M2)
Incoming HV,LV Panel, T.C
Width (Meter)
Roof) (M2)
1X160
14
90
9
2X160
28
118
13.5
1X250
15
91
9
2X250
30
121
13.5
1X400
16.5
93
9
2X400
33
125
13.5
3X400
49.5
167
18
2X500
36
130
14.5
3X500
54
172
19
2X630
36
132
14.5
3X630
54
176
19
2X800
39
135
14.5
3X800
58
181
14
2X1000
39
149
14.5
3X1000
58
197
19
The Capacitor Bank should be automatic Switched type for Sub Station of 5MVA and Higher.
Transformer up to 25KVA can be mounted direct on Pole.
Transformer from 25KVA to 250KVA can be mounted either on “H” Frame of Plinth.
Transformer above 250KVA can be mounted Plinth only.
Transformer above 100MVA shall be protected by Drop out Fuse or Circuit Breaker.
Span of Transmission Line (Central Electricity Authority):
Voltage
Normal Span
765 KV
400 to 450 Meter
400 KV
400 Meter
220 KV
335,350,375 Meter
132 KV
315,325,335 Meter
66 KV
240,250,275 Meter
Max. Lock Rotor Amp for 1 Phase 230 V Motor (NEMA)
HP
Amp
1 HP
45 Amp
1.5 HP
50 Amp
2 HP
65 Amp
3 HP
90 Amp
5 HP
135 Amp
7.5 HP
200 Amp
10 HP
260 Amp
Three Phase Motor Code (NEMA)
HP
Code
<1 HP
L
1.5 to 2.0 HP
L,M
3 HP
K
5 HP
J
7 to 10 HPPHPHPHHHHH
H
>15 HP
G
Service Factor of Motor:
Synchronous Speed (RPM)
HP
3600
1800
1200
900
720
600
514
RPM
RPM
RPM
RPM
RPM
RPM
RPM
1 HP
1.25
1.15
1.15
1.15
1
1
1
1.5 to 1.25
1.15
1.15
1.15
1.15
1.15
1.15
1.15
HP
150 HP
1.15
1.15
1.15
1.15
1.15
1.15
1
200 HP
1.15
1.15
1.15
1.15
1.15
1
1
> 200 HP
1
1.15
1
1
1
1
1
Type of Contactor:
Type
Application
AC1
Non Inductive Load or Slightly Inductive Load
AC2
Slip Ring Motor, Starting, Switching OFF
AC3
Squirrel Cage Motor
AC4,AC5,AC5a,
Rapid Start & Rapid Stop
AC5b,AC6a
AC 5a
Auxiliary Control circuit
AC 5b
Electrical discharge Lamp
AC 6a
Electrical Incandescent Lamp
AC 6b
Transformer Switching
AC 7a
Switching of Capacitor Bank
AC 7b
Slightly Inductive Load in Household
AC 5a
Motor Load in Household
AC 8a
Hermetic refrigerant compressor motor with Manual Reset O/L Relay
AC 8b
Hermetic refrigerant compressor motor with Automatic Reset O/L Relay
AC 12
Control of Resistive Load & Solid State Load
AC 13
Control of Resistive Load & Solid State Load with Transformer Isolation
AC 14
Control of small Electro Magnetic Load (<72 VA)
AC 15
Control of Electro Magnetic Load (>72 VA)
Contactor Coil:
Coil Voltage
Suffix
24 Volt
T
48 Volt
W
110 to 127 Volt
A
220 to 240 Volt
B
277 Volt
H
380 to 415 Volt
L
Electrical Thumb Rules-(Part-7)
SEPTEMBER 16, 2013 7 COMMENTS
Overhead Conductor /Cable Size:
Voltage
KV
KV
LT
Overhead Conductor
Cable Size
ACSR-Panther/Wolf/Dog , AAAC
150,185,300,400,240 mm2 Cable
ACSR-Dog/Recon/Rabbit , AAAC
120, 150,185,300 mm2 Cable
ACSR-Dog/Recon/Rabbit , AAC,AAAC
95,120, 150,185,300 mm2 Cable
Transmission / Distribution Line:
Span
400KV=400 Meter
220KV=350 Meter
132KV=335 Meter
66KV=210 Meter
Conductor Ampere
Dog=300Amp
Panther=514Amp
Zebra=720Amp
Rabbit=208Amp
Moose=218Amp
Height of Tower
400KV=30Meter (Base 8.8 Meter)
220KV=23Meter (Base 5.2 Meter)
220KV Double Circuit=28 Meter
66KV=13Meter
Voltage wise Conductor
400KV=Moose ACSR=500MVA Load
220KV=Zebra ACSR=200MVA Load
132KV=Panther ACSR=75MVA Load
66KV=Dog ACSR=50MVA Load
Type of Tower:
Type
A
B
C
D
Used
Angle/Deviation
Suspension Tower
Up to 2°
Small Angle Tower
2° to 15°
Medium Angle Tower
15° to 30°
Large Angle / Dead End Tower
30° to 60° & Dead End
Tower Swing Angle Clearance (Metal Part to Live Part):
Swing Angle
Live Part to Metal Part Clearance (mm)
66KV
132KV
220KV
400KV
0°
915mm
1530mm
2130mm
3050mm
15°
915mm
1530mm
2130mm
-
22°
-
-
-
3050mm
30°
760mm
1370mm
1830mm
-
44°
-
-
-
1860mm
44°
610mm
1220mm
1675mm
-
Cable Coding (IS 1554) A2XFY / FRLS / FRPVC / FRLA / PILC)
A Aluminium
2X XLPE
Flat Armoured
WWire Armoured
YOuter PVC Insulation Sheath
WSteel Round Wire
WW
Steel double round wire Armoured
YY
Steel double Strip Armoured
FR
Fire Retardation
LS
Low Smoke
LA
Low Acid Gas Emission
WA
Non Magnetic round wire Armoured
FA
Non Magnetic Flat wire Armoured
FF
Double Steel Round Wire Armoured
Corona Ring Size:
Voltage
Size
<170 KV
160mm Ring put at HV end
>170 KV
350mm Ring put at HV end
>275 KV
450mm Ring put at HV end & 350 mm Ring put at Earth end
Load as per Sq.Ft:
Type of Load
Load/Sq.Ft
Industrial
1000 Watt/Sq.Ft
Commercial
30 Watt/Sq.Ft
Domestic
15 Watt/Sq.Ft
Lighting
15 Watt/Sq.Ft
Diversity Factor
0.5
0.8
0.4
0.8
Size of Ventilation Shaft:
Height of Building in meter
Size of ventilation shaft in sq meter
9.0
1.5
12.5
3.0
15 and above
4.0
Minimum size of shaft in meter
1.0
1.2
1.5
Electrical Thumb Rules-(Part-8)
OCTOBER 1, 2013 6 COMMENTS
Accuracy Class of Metering CT:
Metering Class CT
Class
Applications
0.1 To
Precision measurements
0.2
0.5
High grade kilowatt hour meters for commercial grade kilowatt hour meters
3
General industrial measurements
3 OR 5
Approximate measurements
Accuracy Class Letter of CT:
Metering Class CT
Accuracy Class
Applications
B
Metering Purpose
Protection Class CT
C
CT has low leakage flux.
T
CT can have significant leakage flux.
CT accuracy is applicable within the entire range of secondary currents from 5 to 20 times the nominal CT rating. (Typically wound CTs.)
CT accuracy applies at the maximum rated secondary burden at 20 time rated only. The ratio accuracy can be up to four times greater than the listed value, depending on connected burden and fault current. (Typically window, busing, or bar-type CTs.)
Accuracy Class of Protection CT:
Class
Applications
10P5
Instantaneous over current relays & trip coils: 2.5VA
10P10
Thermal inverse time relays: 7.5VA
10P10
Low consumption Relay: 2.5VA
10P10/5
Inverse definite min. time relays (IDMT) over current
10P10
IDMT Earth fault relays with approximate time grading:15VA
5P10
IDMT Earth fault relays with phase fault stability or accurate time grading: 15VA
Electrical Thumb Rules-(Part 1).
Cable Capacity:
For Cu Wire Current Capacity (Up to 30 Sq.mm) = 6X Size of Wire in Sq.mm
Ex. For 2.5 Sq.mm=6×2.5=15 Amp, For 1 Sq.mm=6×1=6 Amp, For 1.5 Sq.mm=6×1.5=9 Amp
For Cable Current Capacity = 4X Size of Cable in Sq.mm ,Ex. For 2.5 Sq.mm=4×2.5=9 Amp.
Nomenclature for cable Rating = Uo/U
where Uo=Phase-Ground Voltage, U=Phase-Phase Voltage, Um=Highest Permissible Voltage
Current Capacity of Equipments:
1 Phase Motor draws Current=7Amp per HP.
3 Phase Motor draws Current=1.25Amp per HP.
Full Load Current of 3 Phase Motor=HPx1.5
Full Load Current of 1 Phase Motor=HPx6
No Load Current of 3 Phase Motor =30% of FLC
KW Rating of Motor=HPx0.75
Full Load Current of equipment =1.39xKVA (for 3 Phase 415Volt)
Full Load Current of equipment =1.74xKw (for 3 Phase 415Volt)
Earthing Resistance:
Earthing Resistance for Single Pit=5Ω ,Earthing Grid=0.5Ω
As per NEC 1985 Earthing Resistance should be <5Ω.
Voltage between Neutral and Earth <=2 Volts
Resistance between Neutral and Earth <=1Ω
Creepage Distance=18 to 22mm/KV (Moderate Polluted Air) or
Creepage Distance=25 to 33mm/KV (Highly Polluted Air)
Minimum Bending Radius:
Minimum Bending Radius for LT Power Cable=12xDia of Cable.
Minimum Bending Radius for HT Power Cable=20xDia of Cable.
Minimum Bending Radius for Control Cable=10xDia of Cable.
Insulation Resistance:
Insulation Resistance Value for Rotating Machine= (KV+1) MΩ.
Insulation Resistance Value for Motor (IS 732) = ((20xVoltage (L-L)) / (1000+ (2xKW)).
Insulation Resistance Value for Equipment (<1KV) = Minimum 1 MΩ.
Insulation Resistance Value for Equipment (>1KV) = KV 1 MΩ per 1KV.
Insulation Resistance Value for Panel = 2 x KV rating of the panel.
Min Insulation Resistance Value (Domestic) = 50 MΩ / No of Points. (All Electrical Points with Electrical fitting & Plugs). Should be less than 0.5 MΩ
Min Insulation Resistance Value (Commercial) = 100 MΩ / No of Points. (All Electrical Points without fitting & Plugs).Should be less than 0.5 MΩ.
Test Voltage (A.C) for Meggering = (2X Name Plate Voltage) +1000
Test Voltage (D.C) for Meggering = (2X Name Plate Voltage).
Submersible Pump Take 0.4 KWH of extra Energy at 1 meter drop of Water.
Lighting Arrestor:
Arrestor have Two Rating=
(1) MCOV=Max. Continuous Line to Ground Operating Voltage.
(2) Duty Cycle Voltage. (Duty Cycle Voltage>MCOV).
Transformer:
Current Rating of Transformer=KVAx1.4
Short Circuit Current of T.C /Generator= Current Rating / % Impedance
No Load Current of Transformer=<2% of Transformer Rated current
Capacitor Current (Ic)=KVAR / 1.732xVolt (Phase-Phase)
Typically the local utility provides transformers rated up to 500kVA For maximum connected load of 99kW,
Typically the local utility provides transformers rated up to 1250kVA For maximum connected load of 150kW.
The diversity they would apply to apartments is around 60%
Maximum HT (11kV) connected load will be around 4.5MVA per circuit.
4No. earth pits per transformer (2No. for body and 2No. for neutral earthing),
Clearances, approx.1000mm around TC allow for transformer movement for replacement.
Diesel Generator:
Diesel Generator Set Produces=3.87 Units (KWH) in 1 Litter of Diesel.
Requirement Area of Diesel Generator = for 25KW to 48KW=56 Sq.meter, 100KW=65 Sq.meter.
DG less than or equal to 1000kVA must be in a canopy.
DG greater 1000kVA can either be in a canopy or skid mounted in an acoustically treated room DG noise levels to be less than 75dBA @ 1meter.
DG fuel storage tanks should be a maximum of 990 Litter per unit Storage tanks above this level will trigger more stringent explosion protection provision.
Current Transformer:
Nomenclature of CT:
Ratio: input / output current ratio
Burden (VA): total burden including pilot wires. (2.5, 5, 10, 15 and 30VA.)
Class: Accuracy required for operation (Metering: 0.2, 0.5, 1 or 3, Protection: 5, 10, 15, 20, 30).
Accuracy Limit Factor:
Nomenclature of CT: Ratio, VA Burden, Accuracy Class, Accuracy Limit Factor.Example: 1600/5, 15VA 5P10 (Ratio: 1600/5, Burden: 15VA, Accuracy Class: 5P, ALF: 10)
As per IEEE Metering CT: 0.3B0.1 rated Metering CT is accurate to 0.3 percent if the connected secondary burden if impedance does not exceed 0.1 ohms.
As per IEEE Relaying (Protection) CT: 2.5C100 Relaying CT is accurate within 2.5 percent if the secondary burden is less than 1.0 ohm (100 volts/100A).
Quick Electrical Calculation
1HP=0.746KW
Star Connection
1KW=1.36HP
Line Voltage=√3 Phase Voltage
1Watt=0.846 Kla/Hr
Line Current=Phase Current
1Watt=3.41 BTU/Hr
Delta Connection
1KWH=3.6 MJ
Line Voltage=Phase Voltage
1Cal=4.186 J
Line Current=√3 Phase Current
1Tone= 3530 BTU
85 Sq.ft Floor Area=1200 BTU
1Kcal=4186 Joule
1KWH=860 Kcal
1Cal=4.183 Joule
Electrical Thumb Rules (Part-2)
Useful Equations:
For Sinusoidal Current : Form Factor = RMS Value/Average Value=1.11
For Sinusoidal Current : Peak Factor = Max Value/RMS Value =1.414
Average Value of Sinusoidal Current(Iav)=0.637xIm (Im= Max.Value)
RMS Value of Sinusoidal Current(Irms)=0.707xIm (Im= Max.Value)
A.C Current=D.C Current/0.636.
Phase Difference between Phase= 360/ No of Phase (1 Phase=230/1=360°,2Phase=360/2=180°)
Short Circuit Level of Cable in KA (Isc)=(0.094xCable Dia in Sq.mm)/√ Short Circuit Time (Sec)
Max.Cross Section Area of Earthing Strip(mm2) =√(Fault Current x Fault Current x Operating Time of Disconnected Device ) / K
K=Material Factor, K for Cu=159, K for Alu=105, K for steel=58 , K for GI=80
Most Economical Voltage at given Distance=5.5x√ ((km/1.6)+(kw/100))
Cable Voltage Drop(%)=(1.732xcurrentx(RcosǾ+jsinǾ)x1.732xLength (km)x100)/(Volt(L-L)x Cable Run.
Spacing of Conductor in Transmission Line (mm) = 500 + 18x (P-P Volt) + (2x (Span in Length)/50).
Protection radius of Lighting Arrestor = √hx (2D-h) + (2D+L). Where h= height of L.A, D-distance of equipment (20, 40, 60 Meter), L=Vxt (V=1m/ms, t=Discharge Time).
Size of Lighting Arrestor= 1.5x Phase to Earth Voltage or 1.5x (System Voltage/1.732).
Maximum Voltage of the System= 1.1xRated Voltage (Ex. 66KV=1.1×66=72.6KV)
Load Factor=Average Power/Peak Power
If Load Factor is 1 or 100% = This is best situation for System and Consumer both.
If Load Factor is Low (0 or 25%) =you are paying maximum amount of KWH consumption. Load Factor may be increased by switching or use of your Electrical Application.
Demand Factor= Maximum Demand / Total Connected Load (Demand Factor <1)
Demand factor should be applied for Group Load
Diversity Factor= Sum of Maximum Power Demand / Maximum Demand (Demand Factor >1)
Diversity factor should be consider for individual Load
Plant Factor(Plant Capacity)= Average Load / Capacity of Plant
Fusing Factor=Minimum Fusing Current / Current Rating (Fusing Factor>1).
Voltage Variation(1 to 1.5%)= ((Average Voltage-Min Voltage)x100)/Average Voltage
Ex: 462V, 463V, 455V, Voltage Variation= ((460-455) x100)/455=1.1%.
Current Variation(10%)= ((Average Current-Min Current)x100)/Average Current
Ex:30A,35A,30A, Current Variation=((35-31.7)x100)/31.7=10.4%
Fault Level at TC Secondary=TC (VA) x100 / Transformer Secondary (V) x Impedance (%)
Motor Full Load Current= Kw /1.732xKVxP.FxEfficiency
Electrical Thumb Rules-(Part-3)
Size of Capacitor for P.F Correction:
For Motor
Size of Capacitor = 1/3 Hp of Motor ( 0.12x KW of Motor)
For Transformer
< 315 KVA
5% of KVA Rating
315 KVA to 1000 KVA
6% of KVA Rating
>1000 KVA
8% of KVA Rating
Earthing Resistance value:
Power Station
0.5 Ω
Sub Station Major
1.0 Ω
Sub Station Minor
2.0 Ω
Distribution Transformer
5.0 Ω
Transmission Line
10 Ω
Single Isolate Earth Pit
5.0 Ω
Earthing Grid
0.5 Ω
As per NEC Earthing Resistance should be <5.0 Ω
Voltage Limit (As per CPWD & Kerala Elect.Board):
Voltage Limit (As Per CPWD)
240V
< 5 KW
415V
<100 KVA
11KV
<3 MVA
22KV
<6 MVA
33KV
<12 MVA
66KV
<20 MVA
110KV
<40 MVA
220KV
>40 MVA
Voltage Variation
> 33 KV
(-) 12.5% to (+) 10%
< 33 KV
(-) 9% to (+) 6%
Low Voltage
(-) 6% to (+) 6%
Insulation Class:
Insulation
Temperature
Class A
105°C
Class E
120°C
Class B
130°C
Class F
155°C
Class H
180°C
Class N
200°C
Standard Voltage Limit:
Voltage
IEC (60038)
IEC (6100:3.6)
Indian Elect. Rule
ELV
< 50 V
LV
50 V to 1 KV
<=1 KV
< 250 V
MV
<= 35 KV
250 V to 650 V
HV
> 1KV
<= 230 KV
650 V to 33 KV
EHV
> 230 KV
> 33 KV
Standard Electrical Connection (As per GERC):
As per Type of Connection
Connection
Voltage
LT Connection
<=440V
HT connection
440V to 66KV
EHT connection
>= 66KV
As per Electrical Load Demand
Up 6W Load demand
1 Phase 230V Supply
6W to 100KVA(100KW)
3 Phase 440V Supply
100KVA to 2500KVA
11KV,22KV,33KV
Above 2500KVA
66KV
HT Connection Earthing
H.T Connection’s Earthing Strip
20mmX4mm Cu. Strip
CT & PT bodies
2Nos
PT Secondary
1Nos
CT Secondary
1Nos
I/C and O/G Cable+ Cubicle Body
2Nos
Standard Meter Room Size (As per GERC):
Meter Box Height
Upper level does not beyond 1.7 meter and Lower level should not
below 1.2 meter from ground.
Facing of Meter Box
Meter Box should be at front area of Building at Ground Floor.
Meter Room / Closed Shade
4 meter square Size
Approximate Load as per Sq.ft Area (As per DHBVN):
Sq.ft Area
Required Load (Connected)
< 900 Sq.ft
8 KW
901 Sq.ft to 1600 Sq.ft
16 KW
1601 Sq.ft to 2500 Sq.ft
20 KW
> 2500 Sq.ft
24 KW
For Flats :100 Sq.ft / 1 KW
For Flats USS /TC: 100 Sq.ft / 23 KVA
Contracted Load in case of High-rise Building:
For Domestic Load
500 watt per 100 Sq. foot of the constructed area.
For Commercial
1500 watt per 100 Sq. foot of the constructed area
For lift, water lifting pump, streetlight if any, corridor/campus
Other Common Load
lighting and other common facilities, actual load shall be
calculated
Staircase Light
11KW/Flat Ex: 200Flat=200×11=2.2KW
Sanctioned Load for Building
Up to 50 Kw
The L.T. existing mains shall be strengthened.
50 kW to 450 kW (500 kVA)
11 kV existing feeders shall be extended if spare capacity is
available otherwise, new 11 kV feeders shall be constructed.
450 kW to 2550 kW (3000 kVA)
11 kV feeder shall be constructed from the nearest 33 kV or 110
kV substation
2550 kW to 8500 kW (10,000 kVA)
33kV feeder from 33 kV or 110 kV sub station
8500 kW (10,000 kVA)
110 kV feeder from nearest 110 kV or 220 kV sub-station
Electrical Thumb Rules-(Part-4)
AUGUST 18, 2013 5 COMMENTS
Sub Station Capacity & Short Circuit Current Capacity:
As per GERC
Voltage
Sub Station Capacity
Short Circuit Current
400 KV
Up to 1000 MVA
40 KA (1 to 3 Sec)
220 KV
Up to 320 MVA
40 KA (1 to 3 Sec)
132 KV
Up to 150 MVA
32 KA (1 to 3 Sec)
66 KV
Up to 80 MVA
25 KA (1 to 3 Sec)
33 KV
1.5 MVA to 5 MVA
35 KA (Urban) (1 to 3 Sec)
11 KV
150 KVA to 1.5 MVA
25 KA (Rural) (1 to 3 Sec)
415 V
6 KVA to 150 KVA
10 KA (1 to 3 Sec)
220 V
Up to 6 KVA
6 KA (1 to 3 Sec)
Sub Station Capacity & Short Circuit Current Capacity:
As per Central Electricity Authority
Voltage
Sub Station Capacity
Short Circuit Current
765 KV
4500 MVA
31.5 KA for 1 Sec
400 KV
1500 MVA
31.5 KA for 1 Sec
220 KV
500 MVA
40 KA for 1 Sec
110/132 KV
150 MVA
40 KA or 50 KA for 1 Sec
66 KV
75 MVA
40 KA or 50 KA for 1 Sec
Minimum Ground Clearance and Fault Clearing Time:
Voltage
Min. Ground Clearance
Fault Clear Time
400 KV
8.8 Meter
100 mille second
220 KV
8.0 Meter
120 mille second
132 KV
6.1 Meter
160 mille second
66 KV
5.1 Meter
300 mille second
33 KV
3.7 Meter
11 KV
2.7 Meter
Bus bar Ampere Rating:
For Phase Bus bar
Aluminium 130 Amp / Sq.cm or 800Amp / Sq.inch.
For Phase Bus bar
Copper 160 Amp / Sq.cm or 1000Amp / Sq.inch
For Neutral Bus bar
Same as Phase Bus bar up to 200 Amp than Size of Neutral Bus bar is at
least half of Phase Bus bar.
Bus bar Spacing:
Between Phase and Earth
26mm (Min)
Between Phase and Phase
32mm (Min)
Bus bar Support between Two Insulator
250mm.
Sound Level of Diesel Generator (ANSI 89.2&NEMA 51.20):
KVA
Max. Sound Level
<9 KVA
40 DB
10 KVA to 50 KVA
45 DB
51 KVA to 150 KVA
50 DB
151 KVA to 300 KVA
55 DB
301 KVA to 500 KVA
60 DB
IR Value of Transformer:
IR Value of Transformer
Voltage
30°C
40°C
50°C
>66KV
600MΩ
300MΩ
150MΩ
22KV to 33KV
500MΩ
250MΩ
125MΩ
6.6KV to 11KV
400MΩ
200MΩ
100MΩ
<6.6KV
200MΩ
100MΩ
50MΩ
415V
100MΩ
50MΩ
20MΩ
Standard Size of MCB/MCCB/ELCB/RCCB/SFU/Fuse:
MCB Up to 63 Amp (80Amp and 100 Amp a per Request)
MCCB
Up to 1600 Amp (2000 Amp as per Request)
ACB
Above 1000 Amp
MCB Rating
6A,10A,16A,20A,32A,40A,50A,63A
MCCB Rating
0.5A,1A,2A,4A,6A,10A,16A,20A,32A,40A,50A,63A,80A,100A
(Domestic Max 6A)
RCCB/ELCB
6A,10A,16A,20A,32A,40A,50A,63A,80A,100A
Sen. of ELCB
30ma (Domestic),100ma (Industrial),300ma
DPIC (Double Pole Iron Clad)
5A,15A,30 A for 250V
main switch
TPIC (Triple Pole Iron Clad)
30A, 60A, 100A, 200 A For 500 V
main switch
DPMCB
5A, 10A, 16A, 32A and 63 A for 250V
TPMCCB
100A,200A, 300Aand 500 A For 660 V
TPN main switch
30A, 60A, 100A, 200A, 300 A For 500 V
TPNMCB
16A, 32A,63A For 500 V, beyond this TPNMCCB: 100A, 200A,
300A, 500 A For 660 V
TPN Fuse Unit (Rewirable)
16A,32A,63A,100A,200A
Change over switch (Off
32A,63A,100A,200A,300A,400A,630A,800A
Load)
SFU (Switch Fuse Unit)
32A,63A,100A,125A,160A,200A,250A,315A,400A,630A
HRC Fuse TPN (Bakelite)
125A,160A,200A,250A,400A.630A
HRC Fuse DPN (Bakelite)
16A,32A,63A
MCB/MCCB/ELCB Termination Wire / Cable
Up to 20A MCB
Max. 25 Sq.mm
20A to 63A MCB
Max. 35 Sq.mm
MCCB
Max. 25 Sq.mm
6A to 45A ELCB
16 Sq.mm
24A to 63A ELCB
35 Sq.mm
80A to 100A ELCB
50 Sq.mm
Electrical Thumb Rules-(Part-5)
SEPTEMBER 1, 2013 4 COMMENTS
Standard Size of Transformer (IEEE/ANSI 57.120):
Single Phase Transformer
Three Phase Transformer
5KVA,10 KVA,15 KVA,25 KVA,37.5
3 KVA,5 KVA,9 KVA,15 KVA,30 KVA,45 KVA,75
KVA,50 KVA,75 KVA,100 KVA,167
KVA,112.5 KVA,150 KVA,225 KVA,300 KVA,500 KVA,750
KVA,250 KVA,
KVA,1MVA,1.5 MVA,2 MVA,2.5 MVA,3.7 MVA,5
333 KVA,500 KVA,833 KVA,1.25
MVA,7.5MVA, 10MVA ,12MVA,15MVA,20MVA ,25MVA,
KVA,1.66 KVA,2.5 KVA,3.33 KVA,5.0
30MVA,37.5MVA ,50MVA ,60MVA,75MVA,100MVA
KVA,6.6 KVA,8.3 KVA,10.0 KVA,12.5
KVA,16.6 KVA,20.8 KVA,25.0
KVA,33.33 KVA
Standard Size of Motor (HP):
Electrical Motor (HP)
1,1.5,2,3,5,7.5,10,15,20,30,40,50,60,75,100,125,150,200,250,300,400,450,500,600,700,
800,900,1000,1250,1250,1500,1750,2000,2250,3000,3500,4000
Approximate RPM of Motor
HP
RPM
< 10 HP
750 RPM
10 HP to 30 HP
600 RPM
30 HP to 125 HP
500 RPM
125 HP to 300 HP
375 RPM
Standard Size of Motor (HP):
Electrical Motor (HP)
1,1.5,2,3,5,7.5,10,15,20,30,40,50,60,75,100,125,150,200,250,300,400,450,500,600,700,
800,900,1000,1250,1250,1500,1750,2000,2250,3000,3500,4000
Motor Line Voltage:
Motor (KW)
Line Voltage
< 250 KW
440 V (LV)
150 KW to 3000KW
2.5 KV to 4.1 KV (HV)
200 KW to 3000KW
3.3 KV to 7.2 KV (HV)
1000 KW to 1500KW
6.6 KV to 13.8 KV (HV)
Motor Starting Current:
Supply
Size of Motor
Max. Starting Current
1 Phase
< 1 HP
6 X Motor Full Load Current
1 Phase
1 HP to 10 HP
3 X Motor Full Load Current
3 Phase
10
HP
2 X Motor Full Load Current
3 Phase
10
HP to 15 HP
2 X Motor Full Load Current
3 Phase
> 15 HP
1.5 X Motor Full Load Current
Motor Starter:
Starter
HP or KW
Starting Current
Torque
DOL
<13 HP(11KW)
7 X Full Load Current
Good
Star-
13 HP to 48 HP
3 X Full Load Current
Poor
Delta
Auto TC
> 48 HP (37 KW)
4 X Full Load Current
Good/ Average
VSD
0.5 to 1.5 X Full Load Current
Excellent
Motor > 2.2KW Should not connect direct to supply voltage if it is in Delta winding
Impedance of Transformer (As per IS 2026):
MVA
% Impedance
< 1 MVA
5%
1 MVA to 2.5 MVA
6%
2.5 MVA to 5 MVA
7%
5 MVA to 7 MVA
8%
7 MVA to 12 MVA
9%
12 MVA to 30 MVA
10%
> 30 MVA
12.5%
Standard Size of Transformer:
Standard Size of Transformer
KVA
Power Transformer (Urban)
3,6,8,10,16
Power Transformer (Rural)
1,1.6,3.15,5
Distribution Transformer
25,50,63,100,250,315,400,500,630
Electrical Thumb Rules-(Part-6)
SEPTEMBER 5, 2013 9 COMMENTS
Transformer Earthing Wire / Strip Size:
Size of T.C or DG
Body Earthing
Neutral Earthing
<315 KVA
25×3 mm Cu / 40×6 mm GI Strip
25×3 mm Cu Strip
315 KVA to 500 KVA
25×3 mm Cu / 40×6 mm GI Strip
25×3 mm Cu Strip
500 KVA to 750 KVA
25×3 mm Cu / 40×6 mm GI Strip
40×3 mm Cu Strip
750 KVA to 1000 KVA
25×3 mm Cu / 40×6 mm GI Strip
50×3 mm Cu Strip
Motor Earthing Wire / Strip Size:
Size of Motor
Body Earthing
< 5.5 KW
85 SWG GI Wire
5.5 KW to 22 KW
25×6 mm GI Strip
22 KW to 55 KW
40×6 mm GI Strip
>55 KW
50×6 mm GI Strip
Panel Earthing Wire / Strip Size:
Type of Panel
Body Earthing
Lighting & Local Panel
25×6 mm GI Strip
Control & Relay Panel
25×6 mm GI Strip
D.G & Exciter Panel
50×6 mm GI Strip
D.G & T/C Neutral
50×6 mm Cu Strip
Electrical Equipment Earthing:
Equipment
Body Earthing
LA (5KA,9KA)
25×3 mm Cu Strip
HT Switchgear
50×6 mm GI Strip
Structure
50×6 mm GI Strip
Cable Tray
50×6 mm GI Strip
Fence / Rail Gate
50×6 mm GI Strip
Earthing Wire (As per BS 7671)
Cross Section Area of Phase, Neutral
Minimum Cross Section area of Earthing Conductor
Conductor(S) mm2
(mm2)
S<=16
S (Not less than 2.5 mm2)
16<S<=35
16
S>35
S/2
Area for Transformer Room: (As per NBC-2005):
Transformer
Min. Transformer
Min. Total Sub Station Area(
Min. Space
Size
Room Area (M2)
Incoming HV,LV Panel, T.C
Width (Meter)
Roof) (M2)
1X160
14
90
9
2X160
28
118
13.5
1X250
15
91
9
2X250
30
121
13.5
1X400
16.5
93
9
2X400
33
125
13.5
3X400
49.5
167
18
2X500
36
130
14.5
3X500
54
172
19
2X630
36
132
14.5
3X630
54
176
19
2X800
39
135
14.5
3X800
58
181
14
2X1000
39
149
14.5
3X1000
58
197
19
The Capacitor Bank should be automatic Switched type for Sub Station of 5MVA and Higher.
Transformer up to 25KVA can be mounted direct on Pole.
Transformer from 25KVA to 250KVA can be mounted either on “H” Frame of Plinth.
Transformer above 250KVA can be mounted Plinth only.
Transformer above 100MVA shall be protected by Drop out Fuse or Circuit Breaker.
Span of Transmission Line (Central Electricity Authority):
Voltage
Normal Span
765 KV
400 to 450 Meter
400 KV
400 Meter
220 KV
335,350,375 Meter
132 KV
315,325,335 Meter
66 KV
240,250,275 Meter
Max. Lock Rotor Amp for 1 Phase 230 V Motor (NEMA)
HP
Amp
1 HP
45 Amp
1.5 HP
50 Amp
2 HP
65 Amp
3 HP
90 Amp
5 HP
135 Amp
7.5 HP
200 Amp
10 HP
260 Amp
Three Phase Motor Code (NEMA)
HP
Code
<1 HP
L
1.5 to 2.0 HP
L,M
3 HP
K
5 HP
J
7 to 10 HPPHPHPHHHHH
H
>15 HP
G
Service Factor of Motor:
Synchronous Speed (RPM)
HP
3600
1800
1200
900
720
600
514
RPM
RPM
RPM
RPM
RPM
RPM
RPM
1 HP
1.25
1.15
1.15
1.15
1
1
1
1.5 to 1.25
1.15
1.15
1.15
1.15
1.15
1.15
1.15
HP
150 HP
1.15
1.15
1.15
1.15
1.15
1.15
1
200 HP
1.15
1.15
1.15
1.15
1.15
1
1
> 200 HP
1
1.15
1
1
1
1
1
Type of Contactor:
Type
Application
AC1
Non Inductive Load or Slightly Inductive Load
AC2
Slip Ring Motor, Starting, Switching OFF
AC3
Squirrel Cage Motor
AC4,AC5,AC5a,
Rapid Start & Rapid Stop
AC5b,AC6a
AC 5a
Auxiliary Control circuit
AC 5b
Electrical discharge Lamp
AC 6a
Electrical Incandescent Lamp
AC 6b
Transformer Switching
AC 7a
Switching of Capacitor Bank
AC 7b
Slightly Inductive Load in Household
AC 5a
Motor Load in Household
AC 8a
Hermetic refrigerant compressor motor with Manual Reset O/L Relay
AC 8b
Hermetic refrigerant compressor motor with Automatic Reset O/L Relay
AC 12
Control of Resistive Load & Solid State Load
AC 13
Control of Resistive Load & Solid State Load with Transformer Isolation
AC 14
Control of small Electro Magnetic Load (<72 VA)
AC 15
Control of Electro Magnetic Load (>72 VA)
Contactor Coil:
Coil Voltage
Suffix
24 Volt
T
48 Volt
W
110 to 127 Volt
A
220 to 240 Volt
B
277 Volt
H
380 to 415 Volt
L
Electrical Thumb Rules-(Part-7)
SEPTEMBER 16, 2013 7 COMMENTS
Overhead Conductor /Cable Size:
Voltage
KV
KV
LT
Overhead Conductor
Cable Size
ACSR-Panther/Wolf/Dog , AAAC
150,185,300,400,240 mm2 Cable
ACSR-Dog/Recon/Rabbit , AAAC
120, 150,185,300 mm2 Cable
ACSR-Dog/Recon/Rabbit , AAC,AAAC
95,120, 150,185,300 mm2 Cable
Transmission / Distribution Line:
Span
400KV=400 Meter
220KV=350 Meter
132KV=335 Meter
66KV=210 Meter
Conductor Ampere
Dog=300Amp
Panther=514Amp
Zebra=720Amp
Rabbit=208Amp
Moose=218Amp
Height of Tower
400KV=30Meter (Base 8.8 Meter)
220KV=23Meter (Base 5.2 Meter)
220KV Double Circuit=28 Meter
66KV=13Meter
Voltage wise Conductor
400KV=Moose ACSR=500MVA Load
220KV=Zebra ACSR=200MVA Load
132KV=Panther ACSR=75MVA Load
66KV=Dog ACSR=50MVA Load
Type of Tower:
Type
A
B
C
D
Used
Angle/Deviation
Suspension Tower
Up to 2°
Small Angle Tower
2° to 15°
Medium Angle Tower
15° to 30°
Large Angle / Dead End Tower
30° to 60° & Dead End
Tower Swing Angle Clearance (Metal Part to Live Part):
Swing Angle
Live Part to Metal Part Clearance (mm)
66KV
132KV
220KV
400KV
0°
915mm
1530mm
2130mm
3050mm
15°
915mm
1530mm
2130mm
-
22°
-
-
-
3050mm
30°
760mm
1370mm
1830mm
-
44°
-
-
-
1860mm
44°
610mm
1220mm
1675mm
-
Cable Coding (IS 1554) A2XFY / FRLS / FRPVC / FRLA / PILC)
A Aluminium
2X XLPE
Flat Armoured
WWire Armoured
YOuter PVC Insulation Sheath
WSteel Round Wire
WW
Steel double round wire Armoured
YY
Steel double Strip Armoured
FR
Fire Retardation
LS
Low Smoke
LA
Low Acid Gas Emission
WA
Non Magnetic round wire Armoured
FA
Non Magnetic Flat wire Armoured
FF
Double Steel Round Wire Armoured
Corona Ring Size:
Voltage
Size
<170 KV
160mm Ring put at HV end
>170 KV
350mm Ring put at HV end
>275 KV
450mm Ring put at HV end & 350 mm Ring put at Earth end
Load as per Sq.Ft:
Type of Load
Load/Sq.Ft
Industrial
1000 Watt/Sq.Ft
Commercial
30 Watt/Sq.Ft
Domestic
15 Watt/Sq.Ft
Lighting
15 Watt/Sq.Ft
Diversity Factor
0.5
0.8
0.4
0.8
Size of Ventilation Shaft:
Height of Building in meter
Size of ventilation shaft in sq meter
9.0
1.5
12.5
3.0
15 and above
4.0
Minimum size of shaft in meter
1.0
1.2
1.5
Electrical Thumb Rules-(Part-8)
OCTOBER 1, 2013 6 COMMENTS
Accuracy Class of Metering CT:
Metering Class CT
Class
Applications
0.1 To
Precision measurements
0.2
0.5
High grade kilowatt hour meters for commercial grade kilowatt hour meters
3
General industrial measurements
3 OR 5
Approximate measurements
Accuracy Class Letter of CT:
Metering Class CT
Accuracy Class
Applications
B
Metering Purpose
Protection Class CT
C
CT has low leakage flux.
T
CT can have significant leakage flux.
CT accuracy is applicable within the entire range of secondary currents from 5 to 20 times the nominal CT rating. (Typically wound CTs.)
CT accuracy applies at the maximum rated secondary burden at 20 time rated only. The ratio accuracy can be up to four times greater than the listed value, depending on connected burden and fault current. (Typically window, busing, or bar-type CTs.)
Accuracy Class of Protection CT:
Class
Applications
10P5
Instantaneous over current relays & trip coils: 2.5VA
10P10
Thermal inverse time relays: 7.5VA
10P10
Low consumption Relay: 2.5VA
10P10/5
Inverse definite min. time relays (IDMT) over current
10P10
IDMT Earth fault relays with approximate time grading:15VA
5P10
IDMT Earth fault relays with phase fault stability or accurate time grading: 15VA
nice blog and Sanjay Technical pioneers in the process of manufacturing and supplying superior quality of Metering Cubicles HT Metering Cubicle in Hyderabad
ReplyDeleteTypically the local utility provides transformers rated up to 1250kVA For maximum connected load of 150kW.
ReplyDeletePower factor*KVA=KW
here
if consider 0.8 power factor means
0.8*1250=1000KW
but answer is 150KW
how it will calculate
Great breakdown of cable capacity! Understanding these thumb rules really helps in choosing the right wire size for safety and efficiency. When dealing with high-voltage systems like 35KV power cables, proper insulation and load calculations become even more critical. A small miscalculation can lead to overheating or failures. This is a good refresher—thanks for sharing!
ReplyDelete